Owners Manual
Installation and Operation
Rugged Water Resistant
Inverter / Charger
Page view 0
1 2 3 4 5 6 ... 43 44

Summary of Contents

Page 1 - OBX-IC2024S-120/60

OBX-IC2024S-120/60 Owner’s ManualInstallation and OperationRugged Water ResistantInverter / Charger

Page 2

8WIRE CONNECTIONSDC WiringTheInverterusesDCbrassbatteryterminalswith8Mx1.00stainlesssteelthreadedstuds.Youcanaccessthe terminals by

Page 3 - TABLE OF CONTENTS

912 V/200 amp-hours-12 V/200 amp-hours-12 V/200 amp-hours- Voltage remains at 12 V 200 Ah + 200 Ah + 200 Ah +

Page 4

106 V Battery Wiring Examples for a 24-volt system-DC DISCONNECT (FUSE OR CIRCUIT BREAKER)----SERIES: 200 amp-hours--DC DISCONNECT (FUSE OR CIRCUIT B

Page 5 - Inverter Maintenance

1112 V Battery Wiring Examples for a 24-volt system-DC DISCONNECT (FUSE OR CIRCUIT BREAKER)--SERIES: 200 amp-hours----SERIES STRING 1 CONNECTS TO INV

Page 6 - IMPORTANT SAFETY INSTRUCTIONS

12AC WiringAC OUT SOCKET• — Maxicon circular molded watertight connector supplies power to the loads using the provided AC cable and plug.AC IN SOCKE

Page 7 - SAFETY AND HUMAN FACTORS

13Follow these steps to wire the Inverter to your system: Open all DC breakers or remove any fuses before connecting wiring. 1. Open all AC breakers o

Page 8 - MOUNTING

14POWERING UP Once all connections are established, it is safe to turn the power on, in the following order: Connect DC power, by closing the DC break

Page 9 - SYSTEM PROTECTION

15THE MATE2 SYSTEM CONTROLLER AND DISPLAYThe MATE serves several functions:Allows you to monitor the Inverter through a series of convenient display s

Page 10 - DC Wiring

16<OFF> —turns o all Inverters connected to the MATE <SRCH> —the Inverter begins search mode if the AC load connected is smaller than all

Page 11 - SERIES/PARALLEL (EXAMPLE)

17The AC INPUT CONTROL screen is called up, allowing the user •to connect or disconnect the Inverter to an AC input source.AC INPUT CONTROLcurrently:

Page 12 - 24-volt Inverter

OutBack Power SystemsOutBack Power Systems is a leader in advanced energy conversion technology. Our products include true sine wave inverter/chargers

Page 13

18PRESS THREE TIMES: The CHARGER CONTROL screen appears. This allows the •operation of the Inverter’s battery charger to be preset for an availa

Page 14 - AC Wiring

19MAIN--------------------------------12:00:30P SUM STATUS SETUP ADVThe user can press the <SUM> soft key to display the Summary screen.F

Page 15

20SETUP SCREENSThe Setup screens allow you to change several settings, to make your system run more smoothly. You can program the amperage size of th

Page 16 - POWERING UP

21SETUP/MATE/SUMMARY---------summary controlBACK TYPE DELAY ROLLMAIN--------------------------------12:00:30P SUM STATUS SETUP ADVSETUP

Page 17 - Mounting the MATE:

22SETUP/MATE/SUMMARY----------summary control BACK TYPE DELAY ROLLAfter selecting FX Only and exiting the SETUP/MATE/SUM/TYPE screen, the SUMMAR

Page 18 - INV Hot Key

23SETUP/MATE/SUMMARY/TYPE--sum screen 19 minutes delay timeBACK INC DEC SETUP/MATE/PAGE2--------------choose category:PG1 SUMRY COM MA

Page 19 - AC IN Hot Key

24•<REPOLL>forcestheMATEto“rediscover”alltheOutBackdevices it is connected to. This must be used any time an OutBack device is moved o

Page 20

25Press <STATUS> on the Main menu to access the STATUS menu. STATUS contains all the meters and mode displays for OutBack products connected to

Page 21 - SUM STATUS SETUP ADV

26STATUS/FX/PAGE1---------------choose categoryMODES METER BATT PG2STATUS/FX/PAGE2---------------choose categoryPG1 ERROR WARN PG3STATUS/FX/PAGE

Page 22 - SETUP SCREENS

27METER ScreensThe METER screens displays current, voltage and wattage measurements, Inverter status, and the version of Inverter software, in this or

Page 23 - SUMMARY SETUP SCREENS

1TABLE OF CONTENTS Welcome to the OutBack Extreme Rugged Water Resistant Inverter/Charger ...2Parts Included

Page 24

28STATUS/FX/MODE-------------P00battery 27.8 vdcactualDOWN STATUS PORT STATUS/FX/METER-------------P00absorb

Page 25 - COMMUNICATION SETUP SCREENS

29STATUS/FX/PAGE2-------------------choose category: PG1 ERROR WARN PG3 ERROR ScreensAllscreensreadstatusas“No”undernormalcondition

Page 26

30 STATUS/FX/WARN-------------P00acin freq Notoo low DOWN UP TOP PORT STATUS/FX/WARN-------------P00acin

Page 27 - STATUS SCREENS

31STATUS/FX/DISCON-----------P00 acin freq Notoo high DOWN STATUS PORT STATUS/FX/DISCON-----------P00 aci

Page 28 - Reading a Status Screen

32INSTALLATION DRAWINGA 30A input breaker (maximum) must be •used with the AC sourceA 30A breaker (maximum) must be used to •protect the output circ

Page 29 - Status Meter Screens

33INSTALLATION CHECK LISTITEM

Page 30 - Status Batt(ery) Screens

34OBX-IC2024S-120/60 Inverter/Charger Specications Nominal DC Input Voltage Range 24 VdcNominal AC Voltage / Frequency 120 Vac / 60 HzContinuousP

Page 31 - Status Error Screens

35AC Input Operating Voltage RangeNote: This is the recommended AC input voltage range to be supplied to the Inverter. Voltages outside of this range

Page 32 - Status Warn(ing) Screens

36INVERTER DEFAULT VALUES (subject to change with upgrades)24 VDC System DEFAULT MINIMUM MAXIMUMFloat Voltage 27.4Vdc 24 Vdc 30 VdcAbsorb Voltage 29

Page 33 - Status Discon(nect) Screens

37MaintenanceFollowing exposure to salt water, rinse all exposed surfaces to prevent corrosion. Recoat the DC lugs •and other exposed conductors wit

Page 34 - INSTALLATION DRAWING

2Welcome to the OutBack Extreme Rugged Water Resistant Inverter/ChargerThe OutBack Extreme Rugged Water Resistant Inverter/Charger (hereafter called t

Page 35 - INSTALLATION CHECK LIST

381-Year Limited Warranty OutBack Extreme Inverter/ChargersOutBackPowerSystems,Inc.(“OutBack”)providesaoneyear(1)limitedwarranty(“Warranty

Page 36 - Rated DC Input Current

39After receiving the RMA number, pack the Product(s) authorized for return, along with a copy of the original purchase invoice and warranty certicat

Page 37

40OUTBACK EXTREME INVERTER/CHARGERLIMITED WARRANTY REGISTRATIONComplete this form and return it to:OutBack Power Systems Inc.19009 62nd Ave. NE • Arli

Page 39 - Troubleshooting

Corporate Headquarters1900962ndAvenueNEArlington,WA98223USAPhone:(+1)360.435.6030www.outbackpower.com900-0046-01-00REVAEuropean Sales Oce

Page 40 - 1-Year Limited Warranty

3Parts IncludedStandard with the OutBack Extreme Rugged Water Resistant Inverter/Charger, Model OBX-IC2024S-120/60:• OneOwner’sManual• OneDCCove

Page 41 - 2008-01-07

4 R EA D FIR ST ! SAVE THESE INSTRUCTIONSRead all instructions and cautionary markings on the Inverter, the batteries and all appropriate sections of

Page 42 - Arlington, WA 98223

5Designthebatteryenclosuretopreventaccumulationandconcentrationofhydrogengasin“pockets”atthe top of the enclosure. Vent the battery com

Page 43

6MOUNTINGTheInverterweighs57.5lbs(26.08kg)andmustbesecuredwithappropriatefastenerstoasturdy•mounting surface capable of supporting i

Page 44

7The equipment ground on each is marked with this symbol: Box lug for grounding the Inverter chassisSYSTEM PROTECTIONElectrical systems are designe